Datasheet

Read the in-depth technical information.

Smoke Alarm

The Visit Smoke Alarm
Art. no. BE1480 

Technical information

Power supply

Battery power:

9 V battery:
Duracell MN1604
Energizer 522 or
Ultralife U9VL-J

Operating time:

Duracell MN1604/Energizer 522 
On the Visit System: Approximately 3 years
On the Fire Alarm System: Approximately 2 years

Ultralife U9VL-J
On the Visit System: Approximately 6 years 
On the Fire Alarm System: Approximately 4 years

Power consumption:

Active: 40 mA
Idle position: < 10 μA

Radio function

Radio frequency:

868,3MHz

Number of Radio Keys: 

64 Radio Keys as standard. Special software can be used to increase these to 256 Radio Keys in increments of 64 per software purchase. Contact the nearest supplier for further information.

Coverage:

The normal coverage between a transmitter and receiver in the Bellman Visit 868 System is approximately 200 metres with a clear line of sight. Coverage is reduced if walls and large objects screen off the signals. Any thick walls constructed of reinforced concrete will greatly affect coverage. The system may also be affected by radio transmitters such as TV transmitters, computers, mobile phones, etc. This means that a unit may work perfectly in one part of the room but not at all in another.

Antenna

The antenna (2) should be straight and pointed directly down to achieve best coverage between Smoke Alarms and receivers within the Visit System.

Activation

Via Test Button (1).
Via the built-in smoke detector.
Via the built-in temperature sensor, if the temperature exceeds approx. 57°C.

Additional information

For indoor use only

Dimensions Ø x H:

100 x 35 mm

Weight:

With battery: 110 g
Without battery: 70 g

Colour:

White 

RESOURCES
MANUAL APPENDIX (EN)